Skip to content
GreenhouseSetup
Menu

Greenhouse heater BTU calculator

The short answer

Greenhouse heat loss in BTU per hour equals the glazed envelope area multiplied by the glazing U-factor and the temperature differential you want to hold, with an allowance for air infiltration. A 6 by 6 ft twin-wall house needs roughly 4,900 BTU per hour to hold 40 degrees F above outside, which a 1500 W electric heater just covers at 5,120 BTU per hour.

1500 W delivers
5,120 BTU/hr
15 A circuit ceiling
About 1,440 W continuous
Twin-wall 4 mm
R-1.54, U-0.65
Infiltration allowance
10 to 25 percent

Researched from published specifications and verified owner reviews · Updated 2026-08-16

Calculator

Heater output required

Enter the house dimensions, the glazing and the temperature difference you want to hold. The result is the heat the envelope loses, which is what the heater must replace.

Heat loss 4,900
Equivalent watts
1,436
Envelope area
190 sq ft
Differential
40 F
Glazing R-value
R-1.54

Researched estimate, not professional engineering or horticultural advice. Results depend on your climate, your structure and your crop. Treat the output as a starting figure to check against local conditions and against the manufacturer's own sizing guidance.

How the calculation works

Greenhouse heat loss follows the standard conduction form used across building science: Q equals A times U times delta T. Area multiplied by the thermal transmittance of the envelope multiplied by the temperature difference across it. Everything else is refinement.

A is the glazed envelope area, not the floor area. This is the input people get wrong and it matters because two houses with the same floor can lose heat at meaningfully different rates. A long narrow 4 by 18 ft house has considerably more surface per square foot of floor than a 8 by 9 ft house of the same 72 square feet, because the perimeter is longer relative to the area enclosed. The calculator computes the envelope properly from walls, two triangular gable ends and two pitched roof planes rather than approximating.

U is the reciprocal of the glazing R-value. Four millimetre twin-wall polycarbonate at R-1.54 has a U-factor of about 0.65, meaning it passes 0.65 BTU per hour through each square foot for each degree F of difference. Single polyethylene film at R-0.87 has a U of about 1.15, so it loses nearly twice as fast through the same area.

Delta T is a decision, not a measurement. It is the difference between the minimum you intend to hold inside and the design low outside. Choosing this figure is the single largest lever you have over the answer, and most growers set it higher than their crops require.

Infiltration is applied as a multiplier, because air leakage through door gaps, vent seals and panel joints scales with the same envelope. Published greenhouse guidance runs from 1.0 for a new tight structure to about 1.25 for an older film house with loose doors. A hobby kit is realistically 1.1 to 1.2, and this is a genuine cost that no glazing upgrade addresses.

Reading the result against a real circuit

The number the calculator produces is only useful set against what you can actually supply, and for most hobby greenhouses that is a hard ceiling rather than a budget question.

A 120 V 15 A circuit supplies 1,800 W at full load. Continuous loads, which a heater is, should not exceed 80 percent of the rating, which is 12 A or about 1,440 W. A 1500 W heater draws 12.5 A and is at or fractionally over that limit on its own, which is why the heated builds on this site specify a dedicated circuit rather than an extension from the garage.

In BTU terms, 1500 W is 5,120 BTU per hour. That covers a 6 by 6 twin-wall house at a 40 degree F differential with a small margin, a 6 by 10 at around 30 degrees, and nothing much larger. If the calculator returns a figure above roughly 5,000 BTU per hour, the honest options are a 240 V circuit, a lower target temperature, better insulation, or a smaller house. Adding a second 1500 W heater on a second circuit is possible and is what the expert build does for redundancy, but two heaters on one 15 A circuit is not.

Outdoor electrical work is governed by local code, and a 240 V run to an outbuilding involves conductor sizing, burial depth, a disconnect, grounding and GFCI protection. This is researched general information rather than professional electrical advice, and that installation is a qualified electrician job. There is orientation in greenhouse electrical and safety.

Lowering the number before buying a bigger heater

Every term in the equation except the temperature difference is fixed by the building. The differential is a choice, and it is free to change.

Lower the target. Holding frost-free at 35 to 40 degrees F rather than a growing minimum of 55 roughly halves the differential in most climates, and halves the heating energy with it. For overwintering tender plants and growing hardy winter greens, the lower figure is also horticulturally correct: plants in low winter light cannot photosynthesize enough to use extra warmth, so heating them to 55 costs money and produces very little growth.

Reduce the area term selectively. Bubble insulation on the north wall and the gable ends effectively raises the R-value of that portion of the envelope, and the north wall contributes almost no useful winter light so the cost is negligible. Sealing door gaps addresses the infiltration multiplier, which is frequently a larger loss than growers assume.

Add thermal mass to flatten the peaks. Water barrels do not reduce the calculated steady-state loss, but they substantially reduce heater runtime around dawn by releasing stored daytime heat. Two 55 gallon barrels hold about 917 pounds of water, absorbing roughly 917 BTU per degree F of rise.

Zone the heat. This is the largest practical lever of all and the calculator cannot express it. Heating a 12 square foot propagation bench to 78 degrees F with mats on a thermostat costs a small fraction of heating an entire house to that temperature, and germination responds to soil temperature rather than air temperature anyway. Hold the house frost-free and heat the root zone.

Field tip

Size to the design low, not the record low

Use a design low temperature that represents a genuinely cold night in your area rather than the coldest reading in local history. Sizing a heater for a once-in-twenty-years event means running an oversized unit that short-cycles for the other nineteen years, which controls temperature worse and costs more to buy. On the rare night that exceeds the design low, accept a few degrees of drop, add a temporary heat source, or throw a layer of fleece over the crop. Row cover laid over plants inside a greenhouse is worth several degrees at the crop for almost nothing.

What the calculator cannot tell you

Three things fall outside this arithmetic and all three matter.

Distribution. The equation gives total loss for the building. It says nothing about whether the heat reaches the far end. A house with ten degrees between one end and the other does not have a capacity problem, it has a circulation problem, and it is solved with a small fan rather than a larger heater. This misdiagnosis is common and expensive.

Wind. Heat loss rises with wind speed across the envelope, and an exposed site can lose substantially more than a sheltered one with identical glazing. A windbreak, or siting the house in the lee of a hedge or building, is a real reduction that no calculator input captures. See siting and orientation.

Solar gain. The calculation is a night-time worst case. During the day a greenhouse frequently needs no heat at all and often needs venting instead, even in winter. The heater sizing question is about the coldest hours before dawn, and the daily energy consumption is much lower than continuous operation at the calculated figure would suggest.

Using the result to choose a heater

Once you have a BTU figure, matching it to a product is straightforward, with one caveat about how outputs are stated.

Electric heater output is exact, because electric resistance heating converts essentially all input energy to heat. Multiply watts by 3.412 to get BTU per hour. A 1500 W Biogreen Palma delivers 5,120 BTU per hour, and there is no efficiency figure to apply because there are no combustion losses and no flue.

Combustion heater output is stated as input rating, and the useful heat delivered is lower. A direct-vent unit such as the 11,000 BTU propane heater loses a share of that up the flue, so the delivered figure is meaningfully below the rated one. Unvented units deliver nearly all the heat into the space and also deliver all the combustion products and water vapour, which is why they are the wrong choice for routine overnight use in a closed structure.

Aim to match rather than substantially exceed the calculated figure. A heater sized 20 percent above the requirement gives useful margin. One sized at double will short-cycle, swing the temperature and cost more in both purchase and standby. Selection by type is covered in best greenhouse heaters and the fuel comparison in electric versus propane.

What the calculator result points you toward

Whatever figure this returns, the same four items determine whether the heat you buy actually holds the house.

Related on this site

Common questions

6 answers

+ How do you calculate greenhouse heating requirements?

Multiply the glazed envelope area by the glazing U-factor and by the temperature difference you want to maintain, then add an allowance for air infiltration of roughly 10 to 25 percent. Envelope area rather than floor area is the correct input, because two houses with identical floor area can have quite different surface areas depending on their proportions and roof geometry.

+ How many BTU do I need for a 10 by 12 greenhouse?

Roughly 10,000 BTU per hour to hold a 40 degree F differential with 4 mm twin-wall glazing, based on about 390 square feet of envelope at U-0.65 plus an infiltration allowance. That is about 2.9 kW, which is well beyond any 120 V circuit, so a house this size needs a 240 V heater or a substantially lower target temperature.

+ What temperature difference should I design for?

Use a design low that represents a genuinely cold night in your area rather than the record low, and set the inside target from what you are growing rather than from comfort. Frost-free at 35 to 40 degrees F suits overwintering and winter greens and is horticulturally correct, since plants in low winter light cannot use extra warmth. Growing warm-season crops needs 55 to 60 F and roughly doubles the energy.

+ Does greenhouse size or shape affect heating cost more?

Both, and shape more than people expect. Heat loss scales with envelope surface area rather than floor area, and a long narrow house has considerably more surface per square foot of floor than a compact one. Larger houses are also proportionally cheaper to heat per square foot of growing space, because gable ends are a fixed cost that gets spread over more length.

+ Should I oversize a greenhouse heater?

By around 20 percent for margin, not by double. A substantially oversized heater short-cycles, which swings the temperature, wears the relay and controls the environment worse than a correctly sized unit. It also costs more to buy. The better use of the same money is insulation and sealing, which reduces the requirement permanently rather than adding capacity that raises the bill every night.

+ Why is my greenhouse colder at one end than the other?

That is a circulation problem, not a capacity problem, and a larger heater will not fix it. A closed greenhouse stratifies and a single heat source creates a warm zone around itself. A small circulation fan running continuously whenever the house is closed evens the temperature out for a few watts, and it also breaks up the still humid air at leaf surfaces that causes fungal disease.

Working out the figures for your own house and season? The Greenhouse Build & Growing Planner is the paid version of these pages: 8 printable worksheets you fill in with your own numbers, plus the full PDF, $29.